From natural gas-fueled combined heat and power (CHP) systems and emergency power for facilities, to renewable biogas energy to support the local grid, or electricity generated from coal mine gases, Caterpillar has a wide range of reliable gas power solutions.
To watch these videos, you will need to accept the use of targeting cookies. Cookies
Specifications
Units: US
Continuous Rating 4300 / 4000 ekW @1.0pf
Fuel Type Natural Gas, Biogas, Coal Gas, Associated Gas, Synthesis Gas, Hydrogen Blend (to 25%)
Maximum Electrical Efficiency 44.1 / 43.8%
See more
Benefits & Features
High Reliability
Anti-knock control and cylinder balancing protect the engine from overload and ensure reliable operation
State-of-the-art turbocharger A140 with Wastegate ensures full performance even under high temperatures and higher altitudes
Higher reliability and lower maintenance costs due to open combustion chamber technology
High Availability, High Profitability
Miller valve timing and optimized compression ratios ensure high efficiency and low fuels costs
More profit for your plant
Long maintenance intervals and general overhaul only after 80,000 oh allow an operation of 10 years without general overhaul
Flexible fields of application also with fluctuating gas qualities due to Total Electronic Management (TEM)
Optimized Lubrication Consumption
Savings of up to 4,000 liters of lube oil per year compared to comparable gensets
Improved components reduce lube oil consumption
Lower operating costs due to 30% lower lube oil consumption in comparison to similar products
See more
Docs & Links
Gas Generator Set 50 and 60 Hz Ratings Guide
CG260 Model Series Brochure
Electric Power Ratings Guide
To watch these videos, you will need to accept the use of targeting cookies. Cookies
Docs & Links
Gas Generator Set 50 and 60 Hz Ratings Guide
CG260 Model Series Brochure
Electric Power Ratings Guide
October 10, 2026
Specifications
Units: US
Generator Set Specifications
Continuous Rating 4300 / 4000 ekW @1.0pf
Fuel Type Natural Gas, Biogas, Coal Gas, Associated Gas, Synthesis Gas, Hydrogen Blend (to 25%)
Maximum Electrical Efficiency 44.1 / 43.8%
Maximum Standby Rating 4500 ekW
Frequency 50 / 60 Hz
RPM 1000 / 900 rpm
Engine Specifications
Engine Model CG260-16
Displacement 16586 in³
Aspiration TA
Bore 10.2 in
Stroke 12.6 in
Generator Set Dimensions
Length 371 in
Width 110 in
Height 133 in
Dry Weight - Genset 117505 lb
Benefits & Features
High Reliability
Anti-knock control and cylinder balancing protect the engine from overload and ensure reliable operation
State-of-the-art turbocharger A140 with Wastegate ensures full performance even under high temperatures and higher altitudes
Higher reliability and lower maintenance costs due to open combustion chamber technology
High Availability, High Profitability
Miller valve timing and optimized compression ratios ensure high efficiency and low fuels costs
More profit for your plant
Long maintenance intervals and general overhaul only after 80,000 oh allow an operation of 10 years without general overhaul
Flexible fields of application also with fluctuating gas qualities due to Total Electronic Management (TEM)
Optimized Lubrication Consumption
Savings of up to 4,000 liters of lube oil per year compared to comparable gensets
Improved components reduce lube oil consumption
Lower operating costs due to 30% lower lube oil consumption in comparison to similar products
Standard Equipment
Air Inlet
One-element single-stage air cleaner with enclosure and sevice indicator
Turbocharger with a water-cooled bearing case for all cylinder
Control Panels
TEM (Total Electronic Management)
Cooling
flange connections for JW inlet and outlet
Jacket water and SCAC thermostats
Electrical jacket water and aftercooler coolant pump
Exhaust
Exhaust waste gate for the CG260-16
Closed crankcase ventilation system
Fuel system
Electronic fuel metering valve
Independently controlled cylinder monitoring and ignition system
Pre-chamber spark plugs
Generator
Busbar connections
Closed-coupled generator result in no torque transmission to the base frame
Reactive droop
3-phase sensing and KVAR/PF control
Grid code generator
Anti-condensation space heater
Winding temperature detectors
Starting/Charging
Compressed air engine start
General
Crankshaft vibration damper and guard
Optional Equipment
Cooling
CHP skid
Grid Code Compliance
50Hz: Germany, Belgium, Great Britain, Italy, Poland, and Netherlands
Related Products
Units: US
View 360