Verified product-page source (readable static HTML text snapshot)
Source: https://powergenserv.com/equipment/generators/gillette/pr-3500/
Original HTML SHA-256: b27060350131a71727c8b312908ac866a7ac7c6aefbe7b80d0972f2fd3a4b891
Overview #
The Gillette PR-3500 is a 350-kilowatt prime-rated natural gas generator on PSI's 21.9L turbocharged V12 — the same engine as the SP-4000/5000 standby series. At 350 kW prime (550 bhp), the V12 runs at conservative loading for unlimited continuous duty. DSE 7420 controller, Stamford S4L1DG alternator.
The V12 at continuous duty — 12-cylinder maintenance reality #
12 cylinders under continuous operation means 12-cylinder ignition service every ~6 weeks (1000 hours). This is a multi-technician, planned maintenance event. The PSI 21.9L V12 at 350 kW prime operates at 550 bhp — 28% below its standby capability — providing excellent thermal margin for sustained operation.
Our service experience #
The PSI V12 at prime duty requires rigorous scheduling discipline. We allocate dedicated service windows for the 12-cylinder ignition service, oil change (49 qt with filters), and air filter replacement at each 250/500/1000-hour interval. The engine is reliable at 350 kW continuous when maintained on schedule.
Engineering specifications
Physical
Length 168 in
Width 82 in
Height 92 in
Wet weight 9,550 lb
Acoustic
Sound @ 7m, full load 81 dBA
Enclosure Sound-attenuated
Fuel system & runtime
BTU/hr @ full load 4,623,000
Photos
Documents & downloads
Spec sheets & manuals
Spec sheet (datasheet)
Service manual
Controller manual
Ready to order this model?
Configure your Gillette PR-3500
Lock the enclosure, fuel system, transfer switch, and add-ons — we'll confirm pricing, availability, and lead time within one business day. Prefer a free-form quote? That option is still here.
Configure & Quote → Just request a quote Download datasheet
Estimate runtime for the Gillette PR-3500
Adjust load percent and tank size to estimate runtime. Pre-filled with this model's spec where available.
Estimate runtime on this tank
Generator size
kW
Fuel
Diesel Natural Gas
Load
25 % load 50 % load 75 % load 100 % load
Fuel demand at 75 % load
3,675,000 BTU/hr ≈ 3675.0 cf/min @ 1,000 BTU/cf
On utility natural gas the runtime is generally unlimited provided the supply line and meter can deliver this BTU/hr at the engine's required inlet pressure (typically 5–14" WC residential, up to 5 psi commercial). Confirm against the OEM's published fuel-pressure spec.
Service intervals
Manufacturer-recommended intervals for the Gillette PR-3500 under standby duty. Field intervals may differ based on load profile, ambient conditions, and fuel quality.
Oil & filter Every 250 hours or 6 months
Coolant change Every 4000 hours
Air filter Every 500 hours
Spark plugs Every 1000 hours
Major overhaul ≈ 15,000 hours
Load bank test Every 12 months
Common failure modes
What we've seen fail on this platform. Use as a service-planning reference, not a diagnostic — actual failure modes depend heavily on duty cycle and maintenance history.
Component Symptom Typical hours Severity
Turbocharger Power loss from continuous high-output duty 10,000+ moderate
Spark plugs / ignition Misfire, rough running under sustained load 1,000+ moderate
Oil degradation Accelerated valve train wear from continuous duty 250+ minor
Frequently Asked Questions
Is this the same 21.9L V12 as the SP-4000/5000 standby? Yes — same PSI 21.9L V12 TCAC engine. The SP-4000 is 400 kW standby, SP-5000 is 500 kW standby. The PR-3500 at 350 kW prime is derated for unlimited continuous operation (550 bhp vs 684-764 bhp standby).
What fuel consumption at 350 kW prime? 4,623 ft3/hr NG at full load. At 75%: 3,556 ft3/hr. At 50%: 2,607 ft3/hr. At 24/7 operation, this requires a high-capacity commercial gas service — coordinate with your utility for sustained continuous supply.
Compatible equipment
Controllers
DSE 7420 MkII Controllers
Transfer switches
ASCO 300 Series ATS Automatic Transfer Switches
ASCO 7000 Series Transfer Switch Automatic Transfer Switches
Eaton ATC-900 Automatic Transfer Switches
Thomson TS840 Automatic Transfer Switch Automatic Transfer Switches
Thomson TS870 Automatic Transfer Switch Automatic Transfer Switches
Thomson TS970 Automatic Transfer Switch Automatic Transfer Switches
More in the PR Series (Prime Gas)
80–540 kW natural gas prime power on PSI engines — continuous duty for remote sites, mining, and off-grid operations.
View all 7 models in this series →
Why we recommend Gillette
When budget and lead time matter for industrial diesel standby, we recommend Gillette. Same John Deere and Volvo engines as the major brands, same UL-2200 certification, same Deep Sea Electronics controllers — at 15-30% less, with 3-7 day lead times that the big OEMs can't touch.
We pitch Gillette for industrial diesel applications where buyers prioritize value and open-architecture serviceability. The John Deere and Volvo engines are the same platforms we service daily across other brands, so our technicians maintain Gillette units with full confidence.
See all Gillette generators →
Similar models
Gillette
Gillette PR-2400
Factory-direct prime-rated gas at 15-30% below major brands. PSI 14.6L V8 engine + DSE controller — continuous duty, no lock-in.
240 kW standby · Natural Gas · Liquid-cooled
240 kW prime-rated natural gas generator. PSI 14.6L V8 turbocharged, Stamford S4L1DD alternator, DSE 7420 MKII. Continuous duty, 3-phase only. Made in USA.
EPA Stationary Spark Ignition 3-phase prime-power remote-site
Compare
Gillette
Gillette PR-5400
Factory-direct prime-rated gas at 15-30% below major brands. PSI 31.8L V12 — Gillette's largest prime gas unit. Continuous duty, no lock-in.
540 kW standby · Natural Gas · Liquid-cooled
540 kW prime-rated natural gas generator. PSI 31.8L V12 turbocharged, Stamford HCI534 alternator, DSE 7420. Continuous duty, 3-phase only. Gillette's largest prime gas unit.
EPA Stationary Spark Ignition 3-phase prime-power remote-site
Compare
Gillette
Gillette SP-3500
Factory-direct at 15-30% below major brands. PSI 14.6L V8 engine + DSE controller — no proprietary lock-in. 3-7 day lead times.
350 kW standby · Natural Gas / LPG · Liquid-cooled
350 kW natural gas / 210 kW LPG stationary standby generator. PSI 14.6L V8 turbocharged engine, Stamford S4L1DF alternator, DSE 7420 MKII. Made in USA.
EPA Stationary Spark Ignition 3-phase commercial hotel
Compare
Services for the Gillette PR-3500
Generator Maintenance
Buy a Generator
Need service or parts for the Gillette PR-3500?
We service every major OEM and stock genuine parts for the most common models.
Get A Quote Or call (209) 229-1990
Last reviewed: May 6, 2026