Verified product-page source (readable static HTML text snapshot) Source: https://powergenserv.com/equipment/generators/gillette/pr-5400/ Original HTML SHA-256: d20a086d5f419e76c3cb8a7aaef86a11cef1b50a7082f64e9d8a6b0495c7e17d Overview # The Gillette PR-5400 is a 540-kilowatt prime-rated natural gas generator — Gillette's largest prime gas unit. PSI's 31.8L V12 at 805 bhp for continuous duty, the same engine as the SP-6500 (650 kW standby). Stamford HCI534 alternator, DSE 7420 controller, three-phase only. At 540 kW continuous natural gas, this serves large industrial operations, mining sites, and remote facilities requiring utility-grade prime power without grid dependency. The PSI 31.8L at continuous duty # The 31.8L V12 runs at 805 bhp prime vs. 966 bhp standby — a comfortable 17% derating. This large displacement provides excellent thermal margin for sustained 24/7 operation. The 6-filter oil system (119 qt with filters) requires planned logistics for service events. Our service experience # At 540 kW prime with 12 cylinders, this is the most complex gas generator service we perform. Each 250-hour oil service and 1000-hour ignition service is a planned multi-technician event. We recommend 24/7 remote monitoring via the DSE 7420's Modbus interface to detect developing issues before they cause unplanned shutdowns. Engineering specifications Physical Length 186 in Width 92 in Height 98 in Wet weight 15,950 lb Acoustic Sound @ 7m, full load 86 dBA Enclosure Sound-attenuated Fuel system & runtime BTU/hr @ full load 5,797,000 Photos Documents & downloads Spec sheets & manuals Spec sheet (datasheet) Controller manual Ready to order this model? Configure your Gillette PR-5400 Lock the enclosure, fuel system, transfer switch, and add-ons — we'll confirm pricing, availability, and lead time within one business day. Prefer a free-form quote? That option is still here. Configure & Quote → Just request a quote Download datasheet Estimate runtime for the Gillette PR-5400 Adjust load percent and tank size to estimate runtime. Pre-filled with this model's spec where available. Estimate runtime on this tank Generator size kW Fuel Diesel Natural Gas Load 25 % load 50 % load 75 % load 100 % load Fuel demand at 75 % load 5,670,000 BTU/hr ≈ 5670.0 cf/min @ 1,000 BTU/cf On utility natural gas the runtime is generally unlimited provided the supply line and meter can deliver this BTU/hr at the engine's required inlet pressure (typically 5–14" WC residential, up to 5 psi commercial). Confirm against the OEM's published fuel-pressure spec. Service intervals Manufacturer-recommended intervals for the Gillette PR-5400 under standby duty. Field intervals may differ based on load profile, ambient conditions, and fuel quality. Oil & filter Every 250 hours or 6 months Coolant change Every 4000 hours Air filter Every 500 hours Spark plugs Every 1000 hours Major overhaul ≈ 15,000 hours Load bank test Every 12 months Common failure modes What we've seen fail on this platform. Use as a service-planning reference, not a diagnostic — actual failure modes depend heavily on duty cycle and maintenance history. Component Symptom Typical hours Severity Turbocharger Power loss from continuous high-output duty 10,000+ moderate Spark plugs / ignition Misfire, rough running under sustained load 1,000+ moderate Oil degradation Accelerated valve train wear from continuous duty 250+ minor Frequently Asked Questions Is the PR-5400 the largest prime gas generator Gillette offers? Yes — the PR-5400 at 540 kW is Gillette's largest prime-rated natural gas generator. It uses the same PSI 31.8L V12 as the SP-6500 standby (650 kW). The PR-5400 also has LPG capability at a reduced output (the spec sheet lists both NG and LPG fuel consumption), making it one of the few prime-rated units with dual-fuel capability at this power class. What fuel consumption at 540 kW prime? 5,797 ft3/hr NG at full load. At 75%: 4,450 ft3/hr. At 50%: 3,254 ft3/hr. This is nearly 5.8 MMBTU/hr of continuous gas demand — requires a dedicated high-capacity gas utility connection. What is the standby-to-prime derating? The SP-6500 (standby) rates this same engine at 650 kW / 966 bhp. The PR-5400 (prime) rates it at 540 kW / 805 bhp — a 17% derating for unlimited continuous hours. This is a more moderate derating than the smaller models because the 31.8L V12 has substantial displacement headroom. Compatible equipment Controllers DSE 7420 MkII Controllers Transfer switches ASCO 300 Series ATS Automatic Transfer Switches ASCO 7000 Series Transfer Switch Automatic Transfer Switches Eaton ATC-900 Automatic Transfer Switches Thomson TS870 Automatic Transfer Switch Automatic Transfer Switches Thomson TS880 Automatic Transfer Switch Automatic Transfer Switches Thomson TS970 Automatic Transfer Switch Automatic Transfer Switches More in the PR Series (Prime Gas) 80–540 kW natural gas prime power on PSI engines — continuous duty for remote sites, mining, and off-grid operations. View all 7 models in this series → Why we recommend Gillette When budget and lead time matter for industrial diesel standby, we recommend Gillette. Same John Deere and Volvo engines as the major brands, same UL-2200 certification, same Deep Sea Electronics controllers — at 15-30% less, with 3-7 day lead times that the big OEMs can't touch. We pitch Gillette for industrial diesel applications where buyers prioritize value and open-architecture serviceability. The John Deere and Volvo engines are the same platforms we service daily across other brands, so our technicians maintain Gillette units with full confidence. See all Gillette generators → Similar models Gillette Gillette PR-3500 Factory-direct prime-rated gas at 15-30% below major brands. PSI 21.9L V12 engine + DSE controller — continuous duty, no lock-in. 350 kW standby · Natural Gas · Liquid-cooled 350 kW prime-rated natural gas generator. PSI 21.9L V12 turbocharged, Stamford S4L1DG alternator, DSE 7420. Continuous duty, 3-phase only. Made in USA. EPA Stationary Spark Ignition 3-phase prime-power remote-site Compare Gillette Gillette SP-5000 Factory-direct at 15-30% below major brands. PSI 21.9L V12 high-output + DSE controller — no proprietary lock-in. 3-7 day lead times. 500 kW standby · Natural Gas / LPG · Liquid-cooled 500 kW natural gas / 300 kW LPG stationary standby generator. PSI 21.9L V12 high-output turbocharged engine, Stamford HCI534 alternator, DSE 7420 MKII. Made in USA. EPA Stationary Spark Ignition 3-phase commercial hotel Compare Gillette Gillette SP-6500 Factory-direct at 15-30% below major brands. PSI 31.8L V12 engine + DSE controller — no proprietary lock-in. 3-7 day lead times. 650 kW standby · Natural Gas · Liquid-cooled 650 kW natural gas stationary standby generator. PSI 31.8L V12 turbocharged engine, Stamford HCI634 alternator, DSE 7420 MKII. Natural gas only. Made in USA. EPA Stationary Spark Ignition 3-phase data-center hospital Compare Services for the Gillette PR-5400 Generator Maintenance Buy a Generator Need service or parts for the Gillette PR-5400? We service every major OEM and stock genuine parts for the most common models. Get A Quote Or call (209) 229-1990 Last reviewed: May 6, 2026