Overview #
The Gillette PR-1300 is a 130-kilowatt prime-rated natural gas generator — the high-output variant of the PSI 8.1L inline-6 platform shared with the PR-1000. Same engine, same enclosure (132 x 52 x 65 in), 30% more output through a higher BMEP calibration. Stamford UCI274F alternator, DSE 7420 MKII controller.
PR-1000 vs. PR-1300: same platform, different output #
If load growth is possible, specifying the PR-1300 on the same foundation as the PR-1000 provides 30 kW of headroom at minimal cost. Both models share identical physical dimensions and enclosure options.
Our service experience #
At 130 kW continuous from 8.1L, the PR-1300 runs at higher thermal loading than the 100 kW PR-1000. The turbocharger and charge air cooler work harder at this calibration — we inspect these components more carefully during service on the PR-1300 than on its lower-output sibling.
Engineering specifications
Physical
Length 132 in
Width 52 in
Height 65 in
Wet weight 5,275 lb
Acoustic
Sound @ 7m, full load 75 dBA
Enclosure Sound-attenuated
Fuel system & runtime
BTU/hr @ full load 1,400,000
Photos
Documents & downloads
Spec sheets & manuals
Spec sheet (datasheet)
Service manual
Controller manual
Alternator manual
Ready to order this model?
Configure your Gillette PR-1300
Lock the enclosure, fuel system, transfer switch, and add-ons — we'll confirm pricing, availability, and lead time within one business day. Prefer a free-form quote? That option is still here.
Configure & Quote → Just request a quote Download datasheet
Estimate runtime for the Gillette PR-1300
Adjust load percent and tank size to estimate runtime. Pre-filled with this model's spec where available.
Estimate runtime on this tank
Generator size
kW
Fuel
Diesel Natural Gas
Load
25 % load 50 % load 75 % load 100 % load
Fuel demand at 75 % load
1,365,000 BTU/hr ≈ 1365.0 cf/min @ 1,000 BTU/cf
On utility natural gas the runtime is generally unlimited provided the supply line and meter can deliver this BTU/hr at the engine's required inlet pressure (typically 5–14" WC residential, up to 5 psi commercial). Confirm against the OEM's published fuel-pressure spec.
Service intervals
Manufacturer-recommended intervals for the Gillette PR-1300 under standby duty. Field intervals may differ based on load profile, ambient conditions, and fuel quality.
Oil & filter Every 250 hours or 6 months
Coolant change Every 4000 hours
Air filter Every 500 hours
Spark plugs Every 1000 hours
Major overhaul ≈ 15,000 hours
Load bank test Every 12 months
Common failure modes
What we've seen fail on this platform. Use as a service-planning reference, not a diagnostic — actual failure modes depend heavily on duty cycle and maintenance history.
Component Symptom Typical hours Severity
Turbocharger Power loss from continuous high-output duty 10,000+ moderate
Spark plugs / ignition Misfire, rough running 1,000+ moderate
Charge air cooler Elevated intake temps, reduced output 8,000+ moderate
Frequently Asked Questions
How does the PR-1300 differ from the PR-1000? Same PSI 8.1L I6 TCAC engine, same enclosure. The PR-1300 is the high-output calibration: 130 kW / 200 bhp (vs 100 kW / 199 bhp). The alternator steps from UCI274E to UCI274F for the higher current demand. Fuel consumption increases modestly: 1,400 ft3/hr vs 1,330 ft3/hr at full load.
What hospital-grade sound options are available? The PR-1300 offers hospital-grade silencer options achieving 84 dBA open / 71 dBA in Level 2 enclosure — among the quietest prime-rated generators available. This makes the PR-1300 suitable for continuous-duty installations near occupied spaces.
Compatible equipment
Controllers
DSE 7420 MkII Controllers
Transfer switches
ASCO 300 Series ATS Automatic Transfer Switches
ASCO 7000 Series Transfer Switch Automatic Transfer Switches
Eaton ATC-900 Automatic Transfer Switches
Thomson TS840 Automatic Transfer Switch Automatic Transfer Switches
Thomson TS870 Automatic Transfer Switch Automatic Transfer Switches
More in the PR Series (Prime Gas)
80–540 kW natural gas prime power on PSI engines — continuous duty for remote sites, mining, and off-grid operations.
View all 7 models in this series →
Why we recommend Gillette
When budget and lead time matter for industrial diesel standby, we recommend Gillette. Same John Deere and Volvo engines as the major brands, same UL-2200 certification, same Deep Sea Electronics controllers — at 15-30% less, with 3-7 day lead times that the big OEMs can't touch.
We pitch Gillette for industrial diesel applications where buyers prioritize value and open-architecture serviceability. The John Deere and Volvo engines are the same platforms we service daily across other brands, so our technicians maintain Gillette units with full confidence.
See all Gillette generators →
Similar models
Gillette
Gillette PR-1000
Factory-direct prime-rated gas at 15-30% below major brands. PSI 8.1L I6 engine + DSE controller — continuous duty, no lock-in.
100 kW standby · Natural Gas · Liquid-cooled
100 kW prime-rated natural gas generator. PSI 8.1L I6 turbocharged, Stamford UCI274E alternator, DSE 7420 MKII. Continuous duty. Made in USA.
EPA Stationary Spark Ignition 3-phase prime-power remote-site
Compare
Gillette
Gillette PR-1800
Factory-direct prime-rated gas at 15-30% below major brands. PSI 11.1L I6 engine + DSE controller — continuous duty, no lock-in.
180 kW standby · Natural Gas · Liquid-cooled
180 kW prime-rated natural gas generator. PSI 11.1L I6 turbocharged, Stamford UCID274J alternator, DSE 7420 MKII. Continuous duty. Made in USA.
EPA Stationary Spark Ignition 3-phase prime-power remote-site
Compare
Gillette
Gillette SP-1500
Factory-direct at 15-30% below major brands. PSI 8.8L turbo V8 + DSE controller — no proprietary lock-in. 3-7 day lead times.
150 kW standby · Natural Gas / LPG · Liquid-cooled
150 kW natural gas / 130 kW LPG stationary standby generator. Made-in-USA commercial gaseous unit with PSI 8.8L turbocharged V8 engine, Stamford alternator, and DSE 7420 MKII controller.
EPA Stationary Spark Ignition 3-phase commercial healthcare
Compare
Services for the Gillette PR-1300
Generator Maintenance
Buy a Generator
Need service or parts for the Gillette PR-1300?
We service every major OEM and stock genuine parts for the most common models.
Get A Quote Or call (831) 375-1463
Last reviewed: May 6, 2026